I've been looking at finishing my basement and am leaning towards using 7/16" OSB over Delta-FL for the subfloor. I was also considering leaving some areas as bare cement (laundry room, utility room, storage) to save some money since I'm not planning to put any real flooring in them.
Will leaving part of the floor uncovered cause any problems seing as Delta-FL is also intended to be a vapor barrier? Obviously the vapor barrier aspect is shot, but is that really a problem? (I also looked at dricore, which seems to take the complete opposite approach by encouraging air circulation.)
If I only do part of the floor, should I still seal the Delta-FL to the walls where possible or just give in to the air circulation approach?
Best Answer
Here's what the Armtec rep had to say:
So I guess not only is it ok, but they consider it a good thing to have some air circulation with unfinished spaces, while keeping the moisture out of the finished rooms.