Does this look like an up to code support beam

code-complianceconstructionsupport

we had an entry way widened a bit which required them to install a longer support beam. I'm absolutely not a professional. But the 2×4's supporting the larger beam don't seem very substantial to me. There's just one under each end of the cross beam.

Does anyone who is more knowledgeable about building practices/codes know if this is up to snuff? The width is about 8.5 feet
support beam over 8.5 foot opening

Best Answer

For an 8.5' span I'd say no. The purpose of the jack studs isn't just to hold up the header - it also helps distribute the load more evenly to the foundation. For that wide of a span the IRC calls for 2 jacks(see R502.5 Allowable girder spans).