I realize it may have been answered but there are so many nuances I want to be sure: I have one (metal) double-gang box with one outdoor light circuit. I want to add a switch for a completely different outdoor light. The two independent circuits would co-exist in the same box. Is this legal? Should I put a warning note in the box there are two power sources (on different breakers) in the box? The obvious danger is someone switching one breaker and thinking the box is safe.
Electrical – 2 switches, 2 circuits, same box
electrical
Related Topic
- Electrical – install two independent gfci outlets in one double-gang box
- Electrical – Need Wiring diagram to Help Rewiring a Bedroom and Bathroom to prepare for smart home system
- Electrical – How to connect a Wink relay when two circuits are involved
- Electrical – converting two lights from two switches to two lights from one switch
- Electrical – Three Circuits In One Box
- Electrical – Tricky Three Gang Box Problems
- Electrical Circuits – Can Dual Function Breakers Share a Box?
Best Answer
I mix multiple circuits in the same box a lot.
I would color the wires for the second circuit differently.
Use gray shrinkwrap or tape on the second circuit's neutrals. Then use brown or blue shrinkwrap or tape on the second circuit's hots.
If the next guy is dumb enough to mix gray neutrals with white neutrals, well, you can do what you can do, but you can't fix stupid.
I for one prefer to also use a differnt color for switched-hot (typically red), so mark the switched-hot for circuit 2 with both brown and red.