Electrical – Entry light switch controls adjacent bedroom lighting

electricallightingrecessed-lightingwiring

I'm new here and may have caused a problem when rewiring to install recessed lighting.

The wiring of my entry area is done in such a way that:

  • Cutting the light on, will cut on the light in the entry area AND provide On/Off capabilities to the adjacent bedroom
  • Cutting the light off, will cut off the light in the entry area AND not provided On/Off capabilities to the adjacent bedroom

A diagram of what this looks like is attached. I'm new to this type of thing and the nearest electrician mentioned it is likely an easy fix but no one has the time (booked out) until 2 weeks earliest…

Does anyone have pointers (tutorials online, books, etc) suggestions or solutions on how to get this working so that the switch is not controlling the other room?

Thanks for looking!
enter image description here

Best Answer

@Ed Beal @NoSparksPlease - so yes, these 2 wires needed to be wire nutted together, leaving only the red connected. That resolved the issue, and i've found this video to explain what was happening https://www.youtube.com/watch?v=wRSgemIxamU (Scenario 2 at the 2:47 mark)

@manassehkatz-Moving 2 Codidact 2 - yes the diagram is showing the light box, not the switch box

@ThreePhaseEel - I will indeed post pictures if this ever happens again -- assuming I can't get a hold of an electrician as the first option.

Thanks for the feedback everyone!