Electrical – Is a grommet needed for romex into this metal junction box

electricaljunction-boxledlight-fixture

I bought a 6-pack of these LED downlights. The metal junction box has knockout holes to run my 14-2 (with ground) wire. I was surprised that the J-box didn't come with grommets after knocking out the hole. Are they required in this application and where does one buy them? Should the grommets fit the romex cable tightly as it enters the box.

enter image description here

enter image description here

Best Answer

You don't use a grommet in this application but rather an appropriate clamp. The correct type depends on what you are connecting here but the usual thing for non-metallic cable is something like this:

enter image description here

https://images.homedepot-static.com/productImages/7b668807-9db0-42c3-86b1-e9ec7481045c/svn/halex-conduit-fittings-20511-64_1000.jpg