I'm running electrical conduit to metal knock out boxes throughout a new construction residential home. The knock out boxes are soley used for POE ethernet. Do the metal knock out boxes need grounded somehow? If so, what is the proper means of doing so?
Electrical – Is it necessary to ground a metal Knock Out Box used solely for POE Ethernet wire
electricalethernetlow-voltagewiring
Related Topic
- Electrical – use normal metal electrical box for outdoor low voltage installation
- Electrical – Box fill calculation for isolated ground receptacles
- Wiring – repurpose this RJ45 setup for phone to run as Ethernet
- Wiring – Where should I (not) place POE ethernet outlets
- Electrical – conduit for ground in metal shop
Best Answer
No, they do not need to be grounded.
If the box contained household voltages, then yes, it would need to be grounded.