A few days ago there was a hot question about wiring with several pictures, here's one. Ignoring all the other issues with this wiring job, on the right hand side we see a green wire nut with the ground to the switch being stabbed through the top of the wire nut. I've only ever seen connections where all ground (or any conductors at all really) exit from the same side of the wire nut. Is this at all to code, and if so where?
Electrical – Is it up to code (anywhere) to have a ground wire poking out the end of a wire nut
code-complianceelectricalwire
Related Topic
- Electrical – Do you connect light stability wires to ground nut
- Electrical – Wiring from Main to Subpanel
- Electrical – Replacing old doorbell transformer – wiring
- Electrical – Grounding in main panel without visible ground wire or ground bar
- Electrical – Have four-conductor feed at detached garage subpanel, how to verify the ground
- Electrical – use green wire in a residential wall box
- Electrical – Old kitchen range only has 3-wires, how to wire correctly to 4 wire circuit
- Electrical wire nut melted
Best Answer
Yes, it's up to code, and you will only find the top hole on green wirenuts that are only used for ground connections.