Electrical – Is this switch properly grounded

electricalgroundingswitch

I replaced a standard single pole switch with an Intermatic ST01 timer switch, into a metal electrical box with three other switches. The switch I was replacing had no ground connection, but some of the others do.

When installing the timer switch, I attached the green ground wire from the switch to a screw at the back of the electrical box. This is my first time doing this, so I wanted to find out if this is properly/safely grounded, or if I missed something.

enter image description here

Best Answer

That screw looks like it's for the wire clamp that secures wiring going through the back of the junction box. Instead, you should connect the green wire with a wire nut to the exposed copper wires that I believe are visible in the bottom of the picture. Make sure to use the proper size wire nut, which is based on the wire size and number of wires being joined together.