Purchased a dual fuel goodman system with CTK04 comfortnet thermostat. The thermostat installtion guide shows wiring of a humidifier to the (2) Hum terminals on the furnace IFC. My furnace model is a comfornet compatible model GMVC950905DX. It can't find (2)Hum terminals on the IFC. Are they re-purposing some of the legacy terminals for the non comfornet communicating thermostat without telling me?
How to connect a humidifier to a Goodman dual fuel heating system
furnace
Related Topic
- Low voltage fuse blowing in furnace
- Does Nest utilize all the benefits of a communicating furnace
- Electrical – Install Common Wire (unable to find terminal or 24 VAC)
- Wiring for humidifier to Goodman gmpn080-4 furnace
- Old furnace with no “C” terminal for wifi thermostat
- HVAC Wiring – Connect C Wire to Furnace/Air Conditioner
- Furnace – Can’t Get Furnace to Run in FAN ONLY Mode Solutions
Best Answer
According to the Installation Instructions for a Goodman GMVC95, there should be a 5" brown wire hanging around, not a terminal.