I am remodeling the master bath and I need to relocate the bath tub. I will be extending the trap about 3-4' from where it is now. I'm wondering if I need to relocate the vent pipe as well. How far can it be from the vent?
Plumbing – How far can I move the bath tub trap from the vent
drain-waste-ventplumbing
Related Topic
- Plumbing – How to connect a bath wall spout intended for copper to a brass water supply outlet
- Plumbing – How to vent a bathtub trap when the drain is routed under the tub
- Plumbing – Have bath tubs ever been considered “self-venting” in plumbing code
- Plumbing – Can (must) P-trap be directly underneath the drain in stand-up shower stall
- Plumbing – How far from the kitchen sink can a vent pipe be
Best Answer
It depends on the diameter of the trap. Under International Building Code use table 906.1.
A 1.5" trap can be 6 feet from the vent (if your trap is only 1.25" the maximum distance is 5 feet).
It looks like you should be fine in your situation.