Plumbing – Why would i have 20 volts a.c.running through the plumbing

plumbing

I am living in a 1964 mobile home and replacing plumbing from city line up. I cut the galvanized going into trailer and got sparks placed meter between two lines and read 20 volts give or take a couple .had replaced under trailer outlet for heat tape but that breaker was off. i ran a jumper from galvanized to city copper for time being .followed ground from breaker box to plumbing to under trailer attached at cross member [rusty cross member ]. Any ideas would be greatly appreciated it is getting cold and i need water badly. Bob

Best Answer

Presumably the metal plumbing was your ONLY ground connection (from both the behavior and your description of the ground wire run.) You might want to have an electrician take a look at the system. In any case adding some driven ground rods tied into the grounding system would be a good idea.