Should I run 1/2“ pex from a manifold to each fixture or 3/4”

pex

Right now my setup is 3/4" cpvc pipe running from the water heater and then branching off into 1/2" cpvc pipe to each fixture. If I buy a manifold will there be a a pressure drop if I run 1/2" pex directly to each fixture?

Every manifold I've looked at has 1/2" outlets so not sure if that is a standard to use 1/2" pipe to each fixture.

Best Answer

The average fixture has no need for 3/4" inch, particularly with homerun piping from a manifold. 3/4" is really only needed for tub fillers with larger tubs, or showers with multiple shower heads.

Running 3/4" hot water lines to fixtures will significantly increase hot water wait times, and should be avoided when not necessary (and for lavatory sinks, I'd strongly recommend 3/8" hot water supply lines).