I am having a problem with the T&P valve opening continuously, on & off. I found the T. stats where bad due to temp settings 140 degrees replaced, the expansion tank full of water replaced also replaced the T&P valve. last thing I will be checking is the water pressure regulating valve. If I open the cold water inlet to the tank open all the way, it opens quicker. what going on ?
Water – Electric water heater T&P popping off
water-heater
Related Topic
- Plumbing – What could be causing water to drip from the relief valve of the new gas water heater, again
- Plumbing – T&P valve draining – expansion tank issues
- Plumbing – Hot water tank cold water is always flowing
- Water – New water heater and expansion tank – low pressure
- Water Pressure – Home Water Pressure Consistently Exceeds 150 PSI
- Water – High water pressure issue from hot water heater
- Water – Gas Water Heater leaking water out of the temperature and pressure valve. Could the water pressure regulator contribute to the issue
Best Answer
You may have a shorted element that will cause water to over heat which in turn will cause the T&P to open regularly/occasionally.